Aerial Bundle Conductor (ABC)

Categories: ,

Description

DESCRIPTION:
Two systems are available, namely:
SELF-SUPPORTING SYSTEM:
Consists of four cores of hard drawn stranded compacted aluminium conductors of the same
cross-sectional area insulated with Carbon loaded XLPE for UV protection
SUPPORTING CORE SYSTEM:
Consists of three phase cores of hard drawn stranded compacted aluminium conductors of
the same cross-sectional area insulated with Carbon loaded XLPE and laid up around a bare
aluminium alloy supporting core
APPLICATIONS:
ABC Cable is used in place of bare conductor overhead distribution systems. It provides a
higher level of safety and reliability and economy with reduced maintenance and operative
costs and reduced risks of vandalism and theft. It is ideal for difficult terrains and urban areas
and is a flexible system that is easier to reroute than the conventional overhead line methods Installation Information

  • Economical
  • Flexible
  • Safe
  • Vandal proof
  • Durable
  • Aesthetically pleasing
  • Adaptable

 

Properties
Specification  : SANS 1418 Part 1 & 2
Temperature Range  : -10°C to 80°C
Voltage Rating  : 600/1000V
Core Identification  : Phase 1,2 and 3 indented, ● Non strain-bearing neutral, 2 longitudinal ribs on
opposite surface 0,5mm x 1,00mm ● Strain- bearing (supporting) neutral, 1
longitudinal rib on one surface 0,5mm x 1,00mm
Packaging  : Available on 500 metre wooden drums

 

Technical Data

Electrical Properties

Cable
Size
Current
Rating
(Note 1)
Short Circuit
Rating
(Note 2)
Conductor
Resistance
@ 20°C
Conductor
Resistance
@ 80°C
Self Supporting System Supporting Core Sytem
Induction
Reacance
@ 50Hz
Impendance
(z) @ 50Hz
at 80°C
Supporting
Core Size
Induction
Reactance
@ 50Hz
Impendance
(z) @ 50Hz
at 80°C
mm² (A) kA (Ω/km) (Ω/km) (Ω/km) (Ω/km) mm² (Ω/km) (Ω/km)
25 105 2,3 1,200 1,490 0,096 1,493 54,6 0,101 1,493
35 144 3,2 0,868 1,078 0,096 1,082 54,6 0,097 1,082
50 183 4,6 0,641 0,796 0,090 0,801 54,6 0,089 0,801
70 228 6,4 0,443 0,550 0,089 0,557 54,6 0,086 0,557
95 277 8,5 0,320 0,397 0,086 0,406 54,6 0,081 0,405
120 322 11,0 0,253 0,314 0,084 0,325 70 0,079 0,324
150 350 13,8 0,206 0,256 0,082 0,269 95 0,079 0,268

 

NOTES:   1.  Continuous current rating are given for ambient temperature of 35°C, and maximum conductor
      temperature of 80°C. For other ambient temperatures use adjoining rating factors
    2.  Short circuit ratings of 1 second duration, for a final conductor temperature of 130°C

 

Temp °C 25 30 35 40 45
Factor 1.11 1.05 1.00 0.94 0.88

 

Mechanical Properties

Cable
Size
Conductor
Diameter
Core
Diameter
Self Supporting System Supporting Core System
Approx.
Assembly
Diameter
Approx.
Assembly
Mass
Maximum
Design
Load
Supporting
Core Size
Approx.
Assembly
Diameter
Approx.
Assembly
Mass
Maximum
Design
Load
Phase Cores Min Max Min Max
mm² (mm) (mm) (A) kA (mm) (kg/km) (kN) mm² (mm) (kg/km) (kN)
25 5,6 6,5 8,4 9,6 25 400 5 54,6 26 507 6
35 6,6 7,5 9,8 11,1 27 540 7 54,6 28 612 6
50 7,7 8,6 10,9 12,3 29 697 9 54,6 32 730 6
70 9,3 10,2 12,9 14,3 33 982 14 54,6 34 944 6
95 11,0 12,0 14,6 16,2 37 1302 19 54,6 38 1183 6
120 12,5 13,5 16,1 17,5 41 1470 24 70 40 1600 8
150 13,9 15,0 17,5 19,2 45 2011 30 95,0 44 1870 13
Above Plus 25mm² Auxiliary Core
25 N/A N/A N/A N/A 25 505 N/A N/A 32 612 N/A
35 32 645 34 717
50 34 802 36 835
70 38 1087 38 1049
95 42 1407 42 1288
120 44 1575 50 1705
150 48 2116 56 1975